Modbus TCP to 7-channel RTD Input Module

Support Ethernet 10/100 Based-T communication
Support protocol Modbus/TCP,TCP/IP,UDP,ICMP,ARP
Support individual channel type setting for PT100, PT1000, Balco 500&Ni
Support isolated input channelSupport 16-bit resolution
Support Accuracy:±0.05% or better

Produktnummer: EX-9015-MTCP Kategori:

Beskrivelse

  • Communication: 10/100 Based-T Ethernet
  • Protocol:  Modbus/TCP, TCP/IP, UDP, ICMP and ARP
  • Led indication: Led for power and Ethernet link status
  • Isolation voltage: 3000VDC

Analog Input:

  • Input: channels 7 differential
  • Input Impedance 1MO Resolution 16-bit
  • Input type: individual channel type setting PT100, PT1000, Balco 500&Ni
  • Input range: PT100 -50°C ~ 150°C ,0°C ~ 100°C ,0°C ~ 200°C ,0°C ~ 400°C ,-200°C ~ 200°C , PT1000 -40°C ~ 160°C Balco 500 -30°C ~ 120°C Ni 604 -80°C ~ 100°C or 0°C ~ 100°C Ni 1000 -60°C ~ 160°C
  • Sampling rate: 12 samples/sec (16-bit)
  • Accuracy: ±0.05% or better
  • Zero drift: ± 3µV/°C
  • Span drift: ±25 ppm/°C
  • CMRR: 150dB min. @50/60Hz
  • Over voltage protection: +/- 35V

Power requirement:

  • Consumption: 2.2W
  • Power input: 10~30VDC (unregulated)

Tilbehør

Ingen tilbehør tilgjengelig

Handlekurv